General specifications:
Product Name: Eaton Moeller® series ETR4 Timing relay
Catalog Number: 031891
Model Code: ETR4-69-A
Product Length/Depth: 103 mm
Product Height: 83 mm
Product Width: 23 mm
Product Weight: 0.11 kg
Certifications: CSA File No.: 012528, VDE 0435, UL 508, CSA-22.2 No. 14, IEC/EN 61000-4-3, Standard IEC/EN 61812, IEC/EN 60947-5-1, IEC/EN 61000-4-2, UL File No.: E29184, UL, UL Category Control No.: NKCR, CE, CSA, CSA Class No.: 3211-03, IEC/EN 61812-1

Product specifications:
Type: Timer relay
Contact Rating: Min. load at contact voltage/current: 12 V/100 mA
Air discharge: 8 kV

10.10 Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating: Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility: Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance: Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures: Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat: Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects: Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation: Meets the product standard's requirements. 10.2.5 Lifting: Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact: Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions: Meets the product standard's requirements.
10.3 Degree of protection of assemblies: Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances: Meets the product standard's requirements. 10.5 Protection against electric shock: Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components: Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections: Is the panel builder's responsibility.
10.8 Connections for external conductors: Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength: Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage: Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material: Is the panel builder's responsibility.

Electric connection type: Screw connection
Operating frequency: 4000 Operations/h
Pollution degree: 2
Power consumption: 2 VA at AC (Pick-up power), 1.8 W at DC (Pick-up power), 2 VA at AC (Sealing power), 1.8 W at DC (Sealing power)
Burst impulse: 2 kV, Supply cable According to IEC/EN 61000-4-4: 1 kV, Signal cable
Climatic proofing: Damp heat, constant, to IEC 60068-2-78, Damp heat, cyclic, to IEC 60068-2-30 Rated impulse withstand voltage (Uimp)4000 V AC, 6000 V AC
Rated operational current (Ie): 3 A at AC-14, 380 V 400 V 415 V, 1.5 A at DC-11, 24 V, 3 A at AC-15, 380 V 400 V 415 V, 3 A at AC-15, 300 V, 3 A at AC-15, 220 V 230 V 240 V, 1.2 A at DC-11, L/R max. 50 ms, 3 A at AC-14, 440 V, 3 A at AC-14, 300 V (NC)
Ambient operating temperature - max: 60 °C
Ambient operating temperature - min: -25 °C
Ambient operating temperature (enclosed) - max: 45 °C
Ambient operating temperature (enclosed) - min: -25 °C
Ambient storage temperature - max: 85 °C
Ambient storage temperature - min: -45 °C
Contact changeover time: 4 ms
Conventional thermal current ith of auxiliary contacts (1-pole, open): 6 A
Equipment heat dissipation, current-dependent Pvid: 0 W
Heat dissipation capacity Pdiss: 0 W
Heat dissipation per pole, current-dependent Pvid: 1.4 W
Nominal current: 3 A
Degree of protection: IP20
Terminals: IP20

Functions: Flashing, pulse initiating, On- and Off-delayed, Pulse generating, Adjustable timing function, Outputs, reversible delayed/undelayed, Off-delayed, Pulse forming, Delay on de-energization, Multi-functional, Fleeting contact on energization, Clock function, starting with pause, variable, Clock function, starting with pulse, variable, On-delayed, Delay-on energization Flashing, starting with pulse, fixed time, Fleeting contact on de-energization, Flashing, starting with pause, fixed time, Pulse shaping

Mains voltage tolerance: 24 – 240 V DC, 24 - 240 V AC (at 50/60 Hz)
Voltage type: AC/DC
Mounting position: As required
Shock resistance: 4 g, Make contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Contact discharge: 6 kV

Overvoltage category: III
Short-circuit protection rating: Max. 6 A gG/gL, fuse, Without welding, Contacts, Max. 6 A gG/gL, Fuse, Short-circuit rating without welding, Contacts
Duty factor: 100 %
Command time: 30 ms, DC, 50 ms, AC
Surge rating: 2 kV, symmetrical, power pulses (Surge), EMC, 4 kV, asymmetrical, power pulses (Surge), EMC, According to IEC/EN 61000-4-5, power pulses (Surge), EMC

Electromagnetic fields:
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
10 V/m at 80 - 1000 MHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)


Pick-up voltage:
0.7 - 1.1 V DC x Uc
0.85 - 1.1 V AC x Uc


Immunity to line-conducted interference: 10 V (according to IEC/EN 61000-4-6)


Radio interference class:
Class B (EN 55011, radiated)
Class B (EN 55011, conducted)


Suitable for: DIN rail (top hat rail) mounting

Safe isolation
250 V AC, Between auxiliary contacts, According to EN 61140
250 V AC, Between coil and auxiliary contacts, According to EN 61140

Lifespan, mechanical:
30,000,000 Operations (DC operated)
30,000,000 Operations (AC operated)
Recovery time: 70 ms (after 100 % time delay)
Repetition accuracy: = 0.5 % (deviation)
Number of contacts (change-over contacts): 1


Rated control supply voltage (Us) at AC, 50 Hz - max: 240 V
Rated control supply voltage (Us) at AC, 50 Hz - min: 24 V
Rated control supply voltage (Us) at AC, 60 Hz - max: 240 V
Rated control supply voltage (Us) at AC, 60 Hz - min: 24 V
Rated control supply voltage (Us) at DC - max: 240 V
Rated control supply voltage (Us) at DC - min: 24 V
Rated operational current for specified heat dissipation (In): 6 A
Rated operational voltage (Ue) at AC - max: 440 V
Static heat dissipation, non-current-dependent Pvs: 1.8 W
Time range - max: 360000 s
Time range - min: 0.05 s
Product category: ETR4 timing relays

Terminal capacity:
1 x (0.5 - 2.5) mm², flexible with ferrule
1 x (20 - 14) AWG, solid or stranded
2 x (0.5 - 1.5) mm², flexible with ferrule
1 x (0.5 - 2.5) mm², solid
2 x (0.5 - 1.5) mm², solid

Rated breaking capacity:
3 A at AC-15 (cos ? = 0.3 220 V)
3 A at AC-14 (cos ? = 0.3 440 V)
1.1 x I? (DC-11 L/R - 40 ms)

Rated making capacity:
1.1 x I? (DC-11 L/R - 40 ms)
48 A (AC-14 cos ? = 0.3 400 V)
50 A (AC-15 cos ? = 0.3 220 V)

Voltage type of operating voltage: AC/DC
Operating voltage at AC, 50 Hz - min: 24 V
Operating voltage at AC, 50 Hz - max: 240 V
Operating voltage at AC, 60 Hz - min: 24 V
Operating voltage at AC, 60 Hz - max: 240 V
Operating voltage at DC - min: 24 V
Operating voltage at DC - max 240 V



New surplus, see photos for details.